Addressable Fire Alarm Smoke Detector Features:
1) It can realize electronic coding and rewrite the address via coder in situ.
2) Within a single-chip microcomputer, it can process the sampling data in real-time, save the latest 144 historical data and realize a curve tracing for the field situation.
3) It has a temperature, humidity and dust accumulation drift compensation function and a sensor fault detection function (fault reporting to fire alarm control panel)
4) Non-polarity, two-bus connection that ensures convenient installation and maintenance.
5) Designed with an upper cover and a lower cover and installed on an independent base, it can be installed, debugged and maintained conveniently.
6) Built-in remote indicator output terminal, drive remote indicator lit when fire alarm
Addressable Fire Alarm Smoke Detector Technical parameters:
Operating Voltage | Loop 24V(18V~28V) |
Standby Current | <0.3mA |
Alarm Current | <1.5mA (without remote indicator) <3.5mA (with remote indicator) |
Fire LED | Red, Flash in polling, and illuminate in alarming. |
Remote indicator output | Polarity-sensitive output, directly connect to remote indicator (built in 10k resistor in series, max. output current is 2mA); The red indicator will blink in the monitoring status or remain lit in the alarm status. |
Programming | Electronically addressed. |
Programming Range | Occupying one address within 1~324. |
Wiring | Loop: two wire, polarity-insensitive |
Environmental Temperature | -10℃~+55℃ |
Relative Humidity | ≤95%, non-condensing |
Material of Enclosure | ABS |
Dimension | Diameter: 100mm Height: 58mm (with the base) |
Mounting Hole Distance | 44.5mm~64.3mm |
Weight | About 128g(with base) |
Operating Voltage | Loop 24V(18V~28V) |