1.Maximum number of Analogue Conventional Detector Inputs: 20 detectors each zone
2.Available Options: 2-4 Zone and 6-8 Zone
3.outputs for Alarm devices: Includes 2 bells/fire relay/ fault relay
4.Auxiliary resettable power output: 24VDC/ 100mA limiting protection
5.Automatic power switchover: mains power and secondary power (from batteries)
6.Independent functional buttons with indication: User friendly interface for easy operation and recognition
7.Access levels to enter the panel
8.Fault supervision and notification: inputs, outputs, system, power, earth, fuse
9.Disablement: zones disablement 10.Evacuation: Fire drills to simulate fire alarm condition on panel
11.Silence: sounders and buzzer silence 12.Walk test: indicators check
AC INPUT | 220VAC 50/60Hz | +10% |
-15% | ||
DC OUTPUT | 24VDC typical | |
Voltage for MCU | 5V for MCU | |
Current at 24VDC from PSE | 450mA standby current | |
Maximum current from PSE | 1A except batteries charge | |
Batteries current | 1.85A maximum, current limited | |
Auxiliary output | 24VDC +/- 10%, 100 mA max, current limited, monitored | |
Batteries | 2*12V/ 2.3Ah sealed lead acid gel, self-regulated * | |
Battery low-voltage protection | 21V | |
Detectors connection allowed each zone | 20 (except MCPs) | |
Zone alarm current | 6mA minimum/ 27mA maximum | |
Sounder output | 2*0.75A maximum | |
Fire Relay | 1A/30VDC maximum | |
Fault Relay | 1A/30VDC maximum | |
Communication protocol | 2 wires RS485 bus system | |
EOL resistor for zone | 6.8K 1W | |
EOL resistor for outputs | 6.8K 1W | |
Fuse for AC Power | 1 A/ 250V glass tube fuse 5 X 20mm | |
Fuse on DC Power | 1A/ 250V glass tube fuse 5 X 20mm | |
Environmental | Class A temperature range: -5 to 40°C (23~104°F) Humidity: 5 to 95% RH, non-condensing | |
Terminal blocks rating | All terminals rated for 12 to18 AWG (0.75 to 2.5 mm2) |