1. Explosion-proof mark: Exd ibⅡCT6
2.Operating voltage: DC24V ± 3V
(polarity)
3. Monitoring Current: ≤60μA
4. Alarm Current: 10mA ~ 30mA
5. Alarm output form: normally open and
closed, a pair of dry contact output
6. Response threshold:
0.10dB / m ~ 0.27 dB / m
7. Alarm reset: power outages
(10s Min, DC2.5V Max)
8. Power Time: ≤10S
9. The highest wind speed:
7.6m / s (1500fpm)
10. Alarm confirmation lightred, inspection does not shine, alarm
shine always
11. protection area: When space height
does not exceed 8m, protected area is
30m2
.
12. Working environment:
Temperature: -10 ℃ ~ + 50 ℃
Relative humidity: ≤95% non-condensing
Atmospheric pressure: 80kPa ~ 110kPa
13. The outlet thread: G20
14. Weight: 1.2kg
1. Strictly prohibited in flammable and
explosive places live demolition.
2. Not to damage the surface explosion
during installation, and keep it clean.
Surface explosion fastening screws
should be tightened evenly, do not pay
attention to proof surface foreign material.
3. Long-term use on a regular basis to
detect performance of the detector is
intact, such as failure or damage to the
special
Industry personnel