Product Features
Addressable Fire Alarm System Loop Isolator Module Feature:
1) In the event of a short circuit isolates faulty parts of the loop
2) Automatically resetting once the fault has cleared
3) LED lights indicate status
Technical parameters
Addressable Fire Alarm System Loop Isolator Technical parameters:
Nominal Line Voltage ( VNOM) | 24V |
Standby Current | <3mA |
Capacity | 32 devices |
Indicate | Yellow (flashes when polling, illuminates in action.) |
Maximum Line Voltage ( VMAX) | 28V |
Minimum Line Voltage ( VMIN) | 16V |
Maximum voltage at which the device isolates ( VSOMAX) | 11V |
Minimum voltage at which the device isolates ( VSOMIN) | 8V |
Maximum voltage at which the device reconnects( VSC MAX) | 4V |
Minimum voltage at which the device reconnects( VSC MIN) | 1.4V |
Maximum rated continuous current with the switch closed ( IC MAX) | 1A |
Maximum rated switching current ( IS MAX) | 3A |
Maximum leakage current with the switch open ( ILMAX) | 15mA |
Maximum series impedance with the switch closed( ZC MAX) | 0.15Ω |
Operating Temperature | -10℃~+55℃ |