1. Maximum power output: 350Watt.
2. Speaker driving mode: constant voltage.
Item | Value |
Panel Name: | Voice Evacuation Control Panel |
Model No.: | AW-VP350 |
Power supply | AC 220V (+10%,-15%, 50Hz) |
Remote control trigger mode: | 24VDC |
Line input sensitivity (rms): | 200mV (external line 1), 900mV (external line 2) |
Frequency response range: | 80Hz ~ 8kHz |
Total harmonic distortion: | <5% |
SNR: | 70dB |
Monitoring power: | 1 W |
Rated output voltage: | 120V (constant voltage mode) |
Rated output power: | 350W |
Operating environment: | Temperature 0 ~ + 40 ℃ relative humidity 95% |
Insulation strength: | AC input to the chassis greater than 50M (DC500 V) Constant voltage output to the chassis greater than 50M (DC500 V) |
Electrical strength: | AC input to the chassis leakage less than 10mA (AC 1250V) |
Product Size: | 406(H) X331(W)X123(T) |
Product net weight: | 13kg |
The below functions are for connecting with AW-FP300 serices addressable fire alarm control panel | |
Network | RS485, twist 2 wire cable for over 1000m |
Maximum panels in one RS485 network | 15 |
Programmable channel in one AW-VP350 panel | 20 |
Total network capacity | 5250Watt |
Connection sockets | |
Mains 220V | Connected with 220VAC mains supply |
Backup power 220V | connected to 220VAC fire control power supply, used for power supply in case of mains failure. |
Constant voltage output (+, -) | Connected with speakers |
485 (A, B) | Communicate with AW-FP300 addressable fire alarm control panel |
Remote control input (+, -) | Connected external excitation signal and trigger emergency broadcast remotely. |
External line 1 | Used to input external sound source to the panel for playing. (Volume adjustable). |
External line 2 | Used to input external sound source to the panel for playing. |
Telephone trunk (L1, L2) | Reserved |
Telephone terminal (A, B) | Reserved |
24V input (+, -) | Reserved |